                     Product Details: 
						                        
 Payment & Shipping Terms: 
							
  | 
                            
| Output Capacity: | 2250/2475kVA | Output Power: | 2000/2200kW | 
|---|---|---|---|
| Genset Type: | Hidier | Engine: | Perkins | 
| Frequency: | 50Hz / 60Hz | Cooling Type: | Water Cooled | 
| Highlight: | Perkins Diesel Generator Set | 
			    	||
Cooling Type Water Cooled Perkins Diesel Generators 2000KW 4-Stroke
| HDP Series HDP2000/ HDP2000S | 
| 
			 Model  | 
			
			 Standby Power  | 
			
			 Prime Power  | 
			
			 Engine  | 
			
			 Alternator  | 
			
			 Control Panel  | 
		|||
| 
			 KVA  | 
			
			 KW  | 
			
			 KVA  | 
			
			 KW  | 
			
			 Stamford  | 
			
			 Hidier(Optional)  | 
			
			 Model  | 
		||
| 
			 HDP2000/S  | 
			
			 2475  | 
			
			 1980  | 
			
			 2250  | 
			
			 1800  | 
			
			 4016-61TRG3  | 
			
			 PI734G  | 
			
			 HD1800  | 
			
			 MRS10  | 
		
| 
			 Spec #1.1 Features  | 
		|
| 
			 1  | 
			
			 Excitation system: self-excited (AREP and PMG are optional)  | 
		
| 
			 2  | 
			
			 ATS (automatic transfer switch) receptacle  | 
		
| 
			 3  | 
			
			 Lockable battery isolator switch  | 
		
| 
			 4  | 
			
			 Stainless galvanized zinc plates with strong corrosion resistance  | 
		
| 
			 5  | 
			
			 Vibration isolators between the engine/alternator and base frame  | 
		
| 
			 6  | 
			
			 Integrated wiring design  | 
		
| 
			 7  | 
			
			 Base fuel tank for at least 8 hours running  | 
		
| 
			 8  | 
			
			 Equipped with an industrial muffler  | 
		
| 
			 9  | 
			
			 50℃ radiator  | 
		
| 
			 10  | 
			
			 Top lifting and steel base frame with forklift holes  | 
		
| 
			 11  | 
			
			 Drainage for fuel tank  | 
		
| 
			 12  | 
			
			 Complete protection functions and safety labels  | 
		
| 
			 13  | 
			
			 IP54 (soundproof sets), IP56 (control system)  | 
		
| 
			 14  | 
			
			 Water jacket preheater, oil heater are available.  | 
		
| 
			 15  | 
			
			 Double air cleaner, spare parts, special tools are available.  | 
		
| 
			 16  | 
			
			 Custom-made is acceptable  | 
		
| Ratings and Performance Data | |||
| Engine Brand & Model: | Perkins 4016-61TRG3 | ||
| Alternator Brand & Model: | Stamford PI734G | ||
| Control System: | ComAp InteliLite®MRS10 | ||
| Noise Level@7m: | 70.9-75.8 | ||
| Frequency & Phase: | 50Hz & 3 Phase | ||
| Engine Speed: RPM | 1500 | ||
| Structure Type: | HDP2000 | ||
| HDP2000S | |||
| Fuel Tank Capacity: L | HDP2000 | / | |
| HDP2000S | / | ||
| Fuel Consumption: l/hr (100% Load) | Prime | 470 | |
| Standby | 529 | ||
| Generator Set | Length (L) | Width (W) | Height (H) | Net Weight kg | 
| Model | mm | mm | mm | |
| HDP2000 | 5000 | 2200 | 3200 | 10500 | 
| HDP2000S | 12200 | 2400 | 3200 | 32700 | 
| 
			 Spec #1.2 Container Calculation  | 
		||||
| 
			 Generator Set Model  | 
			
			 20’GP pcs  | 
			
			 40‘GP pcs  | 
			
			 40‘HQ pcs  | 
			
			 Efficiency  | 
		
| 
			 HDP1500  | 
			
			 N/A  | 
			
			 N/A  | 
			
			 N/A  | 
			
			 N/A  | 
		
| 
			 HDP1500S  | 
			
			 N/A  | 
			
			 N/A  | 
			
			 N/A  | 
			
			 N/A  | 
		
| 
			 Spec#2 Engine Perkins 4016-61TRG3 
  | 
		
			
  | 
		|||||||||||||||||||||||||||||||||
| 
			 Spec #2.2 Engine Output  | 
		|||||||
| 
			 Speed rpm  | 
			
			 Run Type  | 
			
			 Typical Output (Net)  | 
			
			 Engine Power  | 
		||||
| 
			 Gross  | 
			
			 Net  | 
		||||||
| 
			 kVA  | 
			
			 kWe  | 
			
			 kWm  | 
			
			 hp  | 
			
			 kWm  | 
			
			 hp  | 
		||
| 
			 1500  | 
			
			 Prime  | 
			
			 1800  | 
			
			 1440  | 
			
			 1600  | 
			
			 2144  | 
			
			 1500  | 
			
			 2010  | 
		
| 
			 Standby  | 
			
			 2250  | 
			
			 1880  | 
			
			 1975  | 
			
			 2647  | 
			
			 1875  | 
			
			 2513  | 
		|
| 
			 Standby (maximum)  | 
			
			 2500  | 
			
			 2000  | 
			
			 2183  | 
			
			 2925  | 
			
			 2083  | 
			
			 2791  | 
		|
*Subject to conformance with ASTM D6751 and EN14214.
The above ratings represent the engine performance capabilities to conditions specified in ISO 8528/1, ISO 3046/1:1986, BS 5514/1. Derating may be required for conditions outside these; consult Perkins Engines Company Limited. Generator powers are typical and are based on typical alternator efficiencies and a power factor (cos θ) of 0.8.
Fuel specification: BS 2869: Part 2 1998 Class A2 or ASTM D975 D2.
Rating Definitions:
Prime Power: Power available at variable load in lieu of a main power network. Overload of 10% is permitted for 1 hour in every 12 hours operation.
Standby (maximum): Power available at variable load in the event of a main power network failure. No overload is permitted.
| 
			 Spec #2.3 Fuel System  | 
		|||||
| 
			 Type of injection  | 
			
			 Direct  | 
		||||
| 
			 Fuel injection pump  | 
			
			 Rotary  | 
		||||
| 
			 Fuel injector opening pressure  | 
			
			 Multi-hole  | 
		||||
| 
			 Delivery/hour at 1500 rpm  | 
			
			 23MPa  | 
		||||
| 
			 Electronic governor (optional)  | 
			
			 Woodward LCG2  | 
		||||
| 
			 Fuel lift pump  | 
		|||||
| 
			 Fuel lift pump pressure  | 
			
			 Electrical  | 
		||||
| 
			 maximum suction head  | 
			
			 120 - 150 l/h (211 - 264 pt/m)  | 
		||||
| 
			 maximum pressure head  | 
			
			 30 - 75 kPa (4.4 - 10.9 psi) a  | 
		||||
| 
			 Fuel filter spacing  | 
			
			 17 kPa  | 
		||||
| 
			 Governor type  | 
			
			 3.0 m  | 
		||||
| 
			 Torque at the governor output  | 
			
			 Woodward LCG2  | 
		||||
| 
			 Fuel specification  | 
		|||||
| 
			 USA Fed Off Highway - EPA2D 89.330-96  | 
		|||||
| 
			 Europe Off Highway - CEC RF-06-99  | 
		|||||
| 
			 Fuel Consumption  | 
		|||||
| 
			 Engine Speed  | 
			
			 1500 rpm  | 
			
			 1800 rpm  | 
		|||
| 
			 UK g/hr  | 
			
			 l/hr  | 
			
			 UK g/hr  | 
			
			 UK g/hr  | 
		||
| 
			 At Standby Max power  | 
			
			 1.73  | 
			
			 7.9  | 
			
			 1.73  | 
			
			 1.73  | 
		|
| 
			 At Prime Power rating  | 
			
			 1.56  | 
			
			 7.1  | 
			
			 1.56  | 
			
			 1.56  | 
		|
| 
			 75% of prime power  | 
			
			 1.18  | 
			
			 5.4  | 
			
			 1.18  | 
			
			 1.18  | 
		|
| 
			 50% of prime power  | 
			
			 0.85  | 
			
			 3.9  | 
			
			 0.85  | 
			
			 0.85  | 
		|
| 
			 Spec #2.4 Cooling System  | 
		|||
| 
			 Total coolant capacity  | 
		|||
| 
			 Engine only  | 
			
			 73 litres  | 
		||
| 
			 Electropak (engine and radiator):  | 
		|||
| 
			 -temperate  | 
			
			 207 litres  | 
		||
| 
			 -tropical  | 
			
			 210 litres  | 
		||
| 
			 Thermostat operating range  | 
			
			 71 - 85 °C  | 
		||
| 
			 Coolant temperature shutdown  | 
			
			 101 °C rising  | 
		||
| 
			 Coolant immersion heater  | 
			
			 4 kWe each  | 
		||
| 
			 Radiator  | 
		|||
| 
			 Radiator face area  | 
			
			 3,46 m²  | 
		||
| 
			 Material and number of rows:  | 
		|||
| 
			 -charge air and water jacket  | 
			
			 copper, 4 rows  | 
		||
| 
			 Fins per inch and material:  | 
		|||
| 
			 -charge air and water jacket  | 
			
			 brass, 12 rows  | 
		||
| 
			 Water jacket cooling data  | 
		|||
| 
			 Temperate and Tropical -coolant flow  | 
			
			 1020 litres/min  | 
		||
| 
			 -coolant exit temperature (max) .  | 
			
			 98 °C  | 
		||
| 
			 -coolant inlet temperature (min)  | 
			
			 thermostatic control  | 
		||
| 
			 Max permissible external system resistance  | 
			
			 kPa  | 
		||
| 
			 Thermostat operation range  | 
			
			 82 - 93 °C  | 
		||
| 
			 Max. static pressure head on pump  | 
			
			 30.4 kPa  | 
		||
| 
			 Recommended coolant  | 
			
			 50% anti freeze / 50% water. For complete details of recommended coolant specifications, refer to the Operation and Maintenance Manual for this engine model.  | 
		||
| 
			 Duct allowance  | 
		|||
| 
			 Maximum additional restriction (duct allowance) to cooling airflow and resultant minimum airflow  | 
		|||
| 
			 Ambient clearance 50% Glycol  | 
			
			 Duct allowance Pa  | 
			
			 m³/sec  | 
		|
| 
			 N/A  | 
			
			 N/A  | 
			
			 N/A  | 
		|
| 
			 N/A  | 
			
			 N/A  | 
			
			 N/A  | 
		|
| 
			 Spec #2.5 Induction System  | 
		|
| 
			 Maximum static bending moment at rear face of block  | 
			
			 1400 Nm  | 
		
| 
			 Maximum air intake restriction  | 
		|
| 
			 -clean filter.  | 
			
			 2 kPa  | 
		
| 
			 -dirty filter  | 
			
			 4 kPa  | 
		
| 
			 -air filter type  | 
			
			 Medium duty axial flow  | 
		
| 
			 Spec #2.6 Electrical System  | 
		|||||||
| 
			 type  | 
			
			 Insulated return  | 
		||||||
| 
			 alternator  | 
			
			 24 volts with integral regulator  | 
		||||||
| 
			 starter motor  | 
			
			 24 volts  | 
		||||||
| 
			 Starter motor power  | 
			
			 16.4 kW  | 
		||||||
| 
			 Number of teeth on flywheel  | 
			
			 TBA  | 
		||||||
| 
			 Number of teeth on starter motor..  | 
			
			 9  | 
		||||||
| 
			 Minimum cranking speed (0°C)  | 
			
			 126 rpm  | 
		||||||
| 
			 Cold start recommendations  | 
		|||||||
| 
			 Minimum engine cranking speed over TDC  | 
			
			 120 rev/min  | 
		||||||
| 
			 Minimum starting temperature  | 
			
			 Grade of engine lubricating oil  | 
			
			 Battery specifications  | 
		|||||
| 
			 °C  | 
			
			 BS3911 Cold start amps  | 
			
			 SAEJ537 Cold cranking amps  | 
			
			 Number of batteries needed  | 
			
			 Commercial ref number  | 
		|||
| 
			 0  | 
			
			 20W  | 
			
			 540  | 
			
			 740  | 
			
			 1  | 
			
			 647  | 
		||
| 
			 -15  | 
			
			 10W  | 
			
			 540  | 
			
			 740  | 
			
			 1  | 
			
			 647  | 
		||
| 
			 -20  | 
			
			 5W  | 
			
			 600  | 
			
			 780  | 
			
			 1  | 
			
			 655  | 
		||
| 
			 Spec #2.7 Exhaust System  | 
		|
| 
			 Exhaust outlet size (internal)  | 
			
			 2 x 254 mm Table D flanges  | 
		
| 
			 Back pressure for total system  | 
			
			 5 kPa  | 
		
Emissions statement: Constant Speed Engines for use in Industrial, IOPU and ElectropaK applications: Certified against the requirements of EU Stage IIIA (Directives 97/68/EC, as last amended, for mobile applications).
| 
			 Spec #2.8 Lubrication System  | 
		||
| 
			 Lubricating oil capacity  | 
			
			 
  | 
		|
| 
			 -total system capacity  | 
			
			 177 litres  | 
		|
| 
			 -sump maximum  | 
			
			 157,5 litres  | 
		|
| 
			 -oil temperature at normal operating conditions to bearings 105 °C  | 
		||
| 
			 Lubricating oil pressure  | 
		||
| 
			 relief valve opens  | 
			
			 415-470 kPa  | 
		|
| 
			 Min oil pressure  | 
			
			 120 kPa  | 
		|
| 
			 -at maximum no-load speed  | 
			
			 147 kPa  | 
		|
| 
			 Oil flow at rated speed  | 
			
			 /  | 
		|
| 
			 Normal oil temperature  | 
			
			 125 °C  | 
		|
| 
			 Recommended SAE viscosity  | 
		||
| 
			 A single or multigrade oil must be used which conforms API-CH-4 or ACEA E5.  | 
		||
| Spec#3 Alternator Stamford P134G | 
| 
			 CONTROL SYSTEM  | 
			
			 SEPARATELY EXCITED BY P.M.G.  | 
		|||||||
| 
			 A.V.R.  | 
			
			 MX341  | 
			
			 MX321  | 
			
			 
  | 
		|||||
| 
			 VOLTAGE REGULATION  | 
			
			 ± 1 %  | 
			
			 ± 0.5 %  | 
			
			 With 4% ENGINE GOVERNING  | 
		|||||
| 
			 SUSTAINED SHORT CIRCUIT  | 
			
			 REFER TO SHORT CIRCUIT DECREMENT CURVES  | 
		|||||||
| 
			 INSULATION SYSTEM  | 
			
			 CLASS H  | 
		|||||||
| 
			 PROTECTION  | 
			
			 IP23  | 
		|||||||
| 
			 RATED POWER FACTOR  | 
			
			 0.8  | 
		|||||||
| 
			 STATOR WINDING  | 
			
			 DOUBLE LAYER LAP  | 
		|||||||
| 
			 WINDING PITCH  | 
			
			 TWO THIRDS  | 
		|||||||
| 
			 WINDING LEADS  | 
			
			 6  | 
		|||||||
| 
			 MAIN STATOR RESISTANCE  | 
			
			 0.0008 Ohms PER PHASE AT 22°C STAR CONNECTED  | 
		|||||||
| 
			 MAIN ROTOR RESISTANCE  | 
			
			 2.42 Ohms at 22°C  | 
		|||||||
| 
			 EXCITER STATOR RESISTANCE  | 
			
			 16 Ohms at 22°C  | 
		|||||||
| 
			 EXCITER ROTOR RESISTANCE  | 
			
			 0.043 Ohms PER PHASE AT 22°C  | 
		|||||||
| 
			 R.F.I. SUPPRESSION  | 
			
			 BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others  | 
		|||||||
| 
			 WAVEFORM DISTORTION  | 
			
			 NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%  | 
		|||||||
| 
			 MAXIMUM OVERSPEED  | 
			
			 2250 Rev/Min  | 
		|||||||
| 
			 BEARING DRIVE END  | 
			
			 BALL. 6232 C3  | 
		|||||||
| 
			 BEARING NON-DRIVE END  | 
			
			 BALL. 6319 C3  | 
		|||||||
| 
			 
  | 
			
			 1 BEARING  | 
			
			 2 BEARING  | 
		||||||
| 
			 WEIGHT COMP. GENERATOR  | 
			
			 4054 kg  | 
			
			 4022 kg  | 
		||||||
| 
			 WEIGHT WOUND STATOR  | 
			
			 2015 kg  | 
			
			 2015 kg  | 
		||||||
| 
			 WEIGHT WOUND ROTOR  | 
			
			 1697 kg  | 
			
			 1654 kg  | 
		||||||
| 
			 WR² INERTIA  | 
			
			 52.2511 kgm2  | 
			
			 51.3341 kgm2  | 
		||||||
| 
			 SHIPPING WEIGHTS in a crate  | 
			
			 4127kg  | 
			
			 4091kg  | 
		||||||
| 
			 PACKING CRATE SIZE  | 
			
			 216 x 105 x 154(cm)  | 
			
			 216 x 105 x 154(cm)  | 
		||||||
| 
			 
  | 
			
			 50 Hz  | 
			
			 60 Hz  | 
		||||||
| 
			 TELEPHONE INTERFERENCE  | 
			
			 THF<2%  | 
			
			 TIF<50  | 
		||||||
| 
			 COOLING AIR  | 
			
			 2.69 m³/sec 5700 cfm  | 
			
			 3.45 m³/sec 7300 cfm  | 
		||||||
| 
			 VOLTAGE STAR  | 
			
			 380/220  | 
			
			 400/231  | 
			
			 415/240  | 
			
			 440/254  | 
			
			 416/240  | 
			
			 440/254  | 
			
			 460/266  | 
			
			 480/277  | 
		
| 
			 kVA BASE RATING FOR REACTANCE VALUES  | 
			
			 
 2135  | 
			
			 
 2200  | 
			
			 
 2200  | 
			
			 
 2160  | 
			
			 
 2475  | 
			
			 
 2640  | 
			
			 
 2695  | 
			
			 
 2750  | 
		
| 
			 Xd DIR. AXIS SYNCHRONOUS  | 
			
			 3.71  | 
			
			 3.45  | 
			
			 3.20  | 
			
			 2.80  | 
			
			 4.48  | 
			
			 4.27  | 
			
			 3.99  | 
			
			 3.74  | 
		
| 
			 X'd DIR. AXIS TRANSIENT  | 
			
			 0.21  | 
			
			 0.19  | 
			
			 0.18  | 
			
			 0.15  | 
			
			 0.25  | 
			
			 0.24  | 
			
			 0.22  | 
			
			 0.21  | 
		
| 
			 X''d DIR. AXIS SUBTRANSIENT  | 
			
			 0.15  | 
			
			 0.14  | 
			
			 0.13  | 
			
			 0.11  | 
			
			 0.18  | 
			
			 0.17  | 
			
			 0.16  | 
			
			 0.15  | 
		
| 
			 Xq QUAD. AXIS REACTANCE  | 
			
			 2.38  | 
			
			 2.22  | 
			
			 2.06  | 
			
			 1.80  | 
			
			 2.88  | 
			
			 2.75  | 
			
			 2.57  | 
			
			 2.41  | 
		
| 
			 X''q QUAD. AXIS SUBTRANSIENT  | 
			
			 0.28  | 
			
			 0.26  | 
			
			 0.24  | 
			
			 0.21  | 
			
			 0.34  | 
			
			 0.32  | 
			
			 0.30  | 
			
			 0.28  | 
		
| 
			 XL LEAKAGE REACTANCE  | 
			
			 0.03  | 
			
			 0.03  | 
			
			 0.03  | 
			
			 0.03  | 
			
			 0.04  | 
			
			 0.04  | 
			
			 0.04  | 
			
			 0.04  | 
		
| 
			 X2 NEGATIVE SEQUENCE  | 
			
			 0.20  | 
			
			 0.19  | 
			
			 0.18  | 
			
			 0.15  | 
			
			 0.25  | 
			
			 0.23  | 
			
			 0.22  | 
			
			 0.21  | 
		
| 
			 X0 ZERO SEQUENCE  | 
			
			 0.04  | 
			
			 0.04  | 
			
			 0.03  | 
			
			 0.03  | 
			
			 0.05  | 
			
			 0.04  | 
			
			 0.04  | 
			
			 0.04  | 
		
| 
			 REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED  | 
		||||||||
| 
			 T'd TRANSIENT TIME CONST.  | 
			
			 0.16s  | 
		|||||||
| 
			 T''d SUB-TRANSTIME CONST.  | 
			
			 0.01s  | 
		|||||||
| 
			 T'do O.C. FIELD TIME CONST.  | 
			
			 2.89s  | 
		|||||||
| 
			 Ta ARMATURE TIME CONST.  | 
			
			 0.02s  | 
		|||||||
| 
			 SHORT CIRCUIT RATIO  | 
			
			 1/Xd  | 
		|||||||
| Spec#4 Control System ComAp InteliLite® MRS10 | 
| 
			 
 
 
 
  | 
			
| 
			 Spec #4.1 Features  | 
		|
| 
			 1  | 
			
			 Automatic or manual start/stop of the gen-set  | 
		
| 
			 2  | 
			
			 Push buttons for simple control, lamp test  | 
		
| 
			 3  | 
			
			 Lockable battery isolator switch  | 
		
| 
			 4  | 
			
			 Graphic back-lit LCD display 128×64 pixels  | 
		
| 
			 5  | 
			
			 2 LED indicators  | 
		
| 
			 6  | 
			
			 Integrated wiring design  | 
		
| 
			 7  | 
			
			 Parameters adjustable via keyboard or PC  | 
		
| 
			 8  | 
			
			 Generator measurements (50/60 Hz):U1-U3, I1-I3, Hz, kW, kVAr, kVArh, kWh  | 
		
| 
			 9  | 
			
			 Selectable protections alarm/ shutdown  | 
		
| 
			 10  | 
			
			 3 phase Generator protections – Over-/under voltage – Over-/under frequency – Current/voltage asymmetry – Overcurrent/overload  | 
		
| 
			 11  | 
			
			 Analog oil pressure, water, temperature, fuel level, battery, voltage, engine speed (pick-up)  | 
		
| 
			 12  | 
			
			 Configurable programmable inputs and outputs  | 
		
| 
			 13  | 
			
			 Warm-up and cooling functions  | 
		
| 
			 14  | 
			
			 RS232 interface (AT-LINK CONV cable is necessary for IL-MRS 10)  | 
		
| 
			 15  | 
			
			 Dimensions 180×120 mm (front panel)  | 
		
| 
			 16  | 
			
			 Sealed to IP65  | 
		
| 
			 17  | 
			
			 Custom-made is acceptable  | 
		
| 
			 Spec #4.2 Functions  | 
		|
| 
			 Binary inputs/oupputs  | 
			
			 6/6  | 
		
| 
			 Analog inputs  | 
			
			 3  | 
		
| 
			 Pick-up  | 
			
			 -  | 
		
| 
			 AMF function  | 
			
			 -  | 
		
| 
			 Input configuration  | 
			
			 ●  | 
		
| 
			 Output configuration  | 
			
			 ●  | 
		
| 
			 Voltage measurement Gen./Mains  | 
			
			 3ph/-  | 
		
| 
			 Current measurement  | 
			
			 3ph  | 
		
| 
			 KW/KWH measurement  | 
			
			 ●/-  | 
		
| 
			 GCB/MCB control with feedback  | 
			
			 
  | 
		
| 
			 Extension units(periph)  | 
			
			 -  | 
		
| 
			 Communication interfaces  | 
			
			 Rs232  | 
		
| 
			 Modem support  | 
			
			 -  | 
		
| 
			 Battery charging alternator circuit  | 
			
			 ●  | 
		
| 
			 Spec #5 Options  | 
			
			 
  | 
		|
| 
			 Items  | 
			
			 Options  | 
			
			 Select  | 
		
| 
			 Engine  | 
			
			 Water Jacket Preheater  | 
			
			 
  | 
		
| 
			 Oil Preheater  | 
			
			 
  | 
		|
| 
			 Alternator  | 
			
			 Winding Temperature Measuring Instrument  | 
			
			 
  | 
		
| 
			 Alternator Preheater  | 
			
			 
  | 
		|
| 
			 PMG  | 
			
			 
  | 
		|
| 
			 Anti-damp and anti-corrosion treatment  | 
			
			 
  | 
		|
| 
			 Anti-condensation heater  | 
			
			 
  | 
		|
| 
			 Generator Set  | 
			
			 Tools with the machine  | 
			
			 STND  | 
		
| 
			 Fuel System  | 
			
			 Low fuel level alarm  | 
			
			 
  | 
		
| 
			 Automatic fuel feeding system  | 
			
			 
  | 
		|
| 
			 Fuel T-valves  | 
			
			 
  | 
		|
| 
			 Enclosure  | 
			
			 Open Type  | 
			
			 
  | 
		
| 
			 Silent/Super Silent Type  | 
			
			 
  | 
		|
| 
			 Trailer Type  | 
			
			 
  | 
		|
| 
			 Canopy/Enclosure Type  | 
			
			 
  | 
		|
| 
			 Lubricating sys  | 
			
			 Oil with the machine  | 
			
			 
  | 
		
| 
			 Exhaust Sys.  | 
			
			 Protection board from hotness  | 
			
			 
  | 
		
| 
			 Cooling Sys.  | 
			
			 Front heat protection  | 
			
			 
  | 
		
| 
			 Coolant (-30°C)  | 
			
			 
  | 
		|
| 
			 Control System  | 
			
			 Remote Control System  | 
			
			 
  | 
		
| 
			 ATS Control System  | 
			
			 
  | 
		|
| 
			 Auto Synchronizing System  | 
			
			 
  | 
		|
| 
			 Generator Set Output Cabinet  | 
			
			 
  | 
		|
| 
			 Control Panel  | 
			
			 Czech·ComAp  | 
			
			 STND  | 
		
| 
			 China·Hidier  | 
			
			 
  | 
		|
| 
			 Denmark·Deif  | 
			
			 
  | 
		|
| 
			 U.K.·Deepsea  | 
			
			 
  | 
		|
| 
			 Voltages  | 
			
			 415/240V  | 
			
			 
  | 
		
| 
			 400/230V  | 
			
			 
  | 
		|
| 
			 380/220V  | 
			
			 
  | 
		|
| 
			 220/127V  | 
			
			 
  | 
		|
| 
			 200-115V  | 
			
			 
  | 
		|
Contact Person: Mr. wei
Tel: 18990909900
Fax: 86-190-457-3333